Wednesday 11 January 2017

KELVINATOR – ELECTROLUX INVERTER SPLIT SYSTEM Fault codes, blinking codes and repair procedure - Part - 2

KSV 26CRE, KSV 35CRE, KSV 70CRE, KSV 26HRE, KSV 35HRE, KSV 53HRE, KSV 62HRE, KSV 70HRE and  KSV 80HRE Models
Communication Fault

*  Disconnect the main power supply to the indoor unit by means of the isolation switch. After approximately one minute, turn the power supply back on & attempt to operate the unit in “Auto” mode with a set temperature of two degrees above or below the ambient temperature.
If the Communication fault has not cleared:
*  Check for supply voltage at the following points.
• Between the Active -Out & Neutral points on the indoor PCB.
• Between the Active & Neutral points on the indoor terminal block.
• Between the Active & Neutral points on the outdoor terminal block.
• Between the Active & Neutral points on the outdoor PCB.
Note: If all the above checks relating to the supply voltage points have been completed, yet the error code still exists, continue:
* Disconnect the supply power & check the continuity of the COM-U wire from the following
points:
> COM-U terminal point on the indoor PCB.
> To the communication terminal points on the indoor terminal block.
> To the communication terminal points on the outdoor terminal block.
Note: When checking the continuity between the indoor terminal block & the outdoor terminal block, disconnect the COM-U & Active wires on the indoor terminal block, then attach them together. This will create a circuit that can then be tested between the COM-U & Active terminal points on the outdoor terminal block.
Note: If all the above checks relating to the COM-U points have been completed, yet the error code still exists, continue.
* Check the continuity of the reactor. If open circuit, change it.
* If the reactor is okay, replace the outdoor PCB assembly.
H5, Indoor unit.
Yellow LED, Outdoor flashing 10 times.
(IPM Protection)
* Disconnect the supply power to the unit by means of the isolation switch.
* Remove the Blue-U, Yellow-V & Red-W flag terminals from the compressor, then measure the resistance value of each winding from these points.
Note: The resistance value should be the same across any terminal combination.
# If all resistance checks are okay, replace the outdoor PCB assembly.
F3 Indoor unit.
Red LED, Outdoor flashing 6 times.
(Outdoor Ambient Sensor)
F4, Indoor unit.
Red LED, Outdoor flashing 5 times.
(Outdoor Coil Sensor)
F5, Indoor unit.
Red LED, Outdoor flashing 7 times.
(Outdoor Compressor Discharge Sensor)
* Check the Condenser Coil, Outdoor Ambient & Compressor Discharge triple point sensor plug for correct connection.
* Check the continuity of each individual sensor, if anyone of the sensors is open circuit; replace the complete triple connector plug assembly.
Note: If all the above checks relating to the sensors & wiring have been completed, yet the error code still exists, replace the main outdoor PCB.
F1, Indoor unit.
(Room Temp Sensor Failure)
F2, Indoor unit.
(Tube Temp Sensor Failure)
* Check the Indoor Ambient & Indoor Tube sensors for correct connection.
* Check the continuity of the relevant sensor, if the sensor is open circuit, change it.
Note: If all the above checks relating to the sensors & wiring have been completed, yet the error code still exists, replace the indoor PCB.
H6, Indoor unit.
(Indoor Fan Stall)
* Check to see if the indoor barrel type fan blade is turning freely.
* Check the evaporator fan motor for correct operation. If the fan motor is not operating check if both three pin AC-Motor connector plugs are anchored correctly to the indoor PCB.
* Check for AC voltage between the Brown & Red wires located on the upper AC-Motor connector plug:
Cooling Mode
Heating Mode
1 speed: 192 Volts AC.
1 speed: 185 Volts AC.
2 speed: 220 Volts AC.
2 speed: 215 Volts AC.
3 speed: 290 Volts AC.
3 speed: 235 Volts AC.
Note: The above AC voltage readings can fluctuate within a range of 10 volts.
* Remove the three pin upper AC-Motor connector plug & check the resistance value from the following points:
> Brown & White (332 ohms)
Note: If the above AC voltage checks are not available, replace the main indoor PCB assembly.
Note: If the above resistance values are not available, replace the indoor fan motor.
L3, Indoor unit.
Red LED, Outdoor flashing 14 times.
(Outdoor DC Fan Motor Malfunction)
* Check the condenser fan for correct operation. If the fan motor is not operating check the three pin DC-Motor connector plug for correct termination to the outdoor PCB.
* With the unit set in heating or cooling mode (depending on ambient conditions) Check for DC
voltage from the points illustrated below, located on the main outdoor PCB.
> Red & Yellow wires: < 13 Volts DC.
> Red & White wires: < 13 Volts DC.
H3, Indoor unit.
Yellow LED, Outdoor flashing 8 times.
(Compressor Overload Protection)
* Check the following points:
> Refrigerant charge.
> Restrictions within the capillary tube.
> Poor air flow across the indoor & outdoor coils.
> Correct operation of the four-way reversing valve.
*  Check the compressor Over Temperature connector plug located on the outdoor PCB for correct termination & continuity to the over temperature protector.
*  Check the over temperature protector located next to the three compressor terminals.
Note: This over temperature protector is “normally closed”.
C5, Indoor unit.
(Jumper Cap Malfunction)
* Check the Jumper Cap for correct termination to the indoor PCB.
Note: If the Jumper Cap is correctly terminated, yet the C5 fault still exists, replace the indoor PCB assembly.
KSV53HRC, KSV62HRC, KSV70CRC, KSV70HRC & KSV80HRC Indoor and Outdoor description
Description – (Indoor)

Description – (Outdoor)
D16 LED Green
D30 LED Red
D6 LED Orange
D5 LED Yellow
Page Nº
Anti-Freezer Limit – Frequency Drop
On
On
On
Off
85
IPM Over Temperature Limit
On
On
On
Flashing
85
Compressor Discharge High Temp Protection
On
Off
On
Flashing
81
Anti-High Temperature Protection
On
Off
On
On
82
Anti-Freeze Protection
On
Off
On
Off
85
4-Way Valve Malfunction
On
Off
Flashing
Off
84
Anti-High Temperature Protection
On
Off
Flashing
Flashing
85
IPM High Temperature Protection
On
Off
Flashing
On
86
Refrigeration System Blocked or Gas Leakage
On
Flashing
On
Off
100
Low Voltage Protection
Off
On
On
Off
83
High Voltage Protection
Off
On
Off
Flashing
83
Drop in Supply Voltage
Off
On
On
On
86
Capacitor Charge Malfunction
Off
On
Off
On
91
AC Over-Current Protection
Off
On
Flashing
Off
81
AC Current Detect Circuit Malfunction
Off
On
Flashing
On
84
PFC Protection
Off
On
Flashing
Flashing
83
Loading EEPROM Malfunction
Off
Off
Off
On
82
IPM Sensor Circuit Malfunction
Off
Off
On
Flashing
83
Communication Fault
Off
Off
Off
Flashing
87 to 90
Outdoor Ambient Sensor
Off
Off
Flashing
On
94
Outdoor Coil Sensor
Off
Off
Flashing
Off
94
Outdoor Compressor Discharge Sensor
Off
Off
Flashing
Flashing
94
System Pressure to High
Off
Flashing
On
Flashing
82
Compressor Phase Detection Circuit Malfunction
Off
Flashing
On
Off
84
Compressor Current Out of Normal Range
Off
Flashing
Off
Off
86
Start-up Failure
Off
Flashing
Off
Flashing
92
IPM Protection
Off
Flashing
Off
On
93
Compressor Overload Protection
Off
Flashing
Flashing
Off
98

LG 32LK610BPUA, LG 32LK610BBUA LCD TVs – How to upgrade the software, fault checking method

  Software update procedure USB (1) Insert the USB memory Stick to the USB port (2) Automatically detect the SW Version and show the bel...